provided equipment | Dust filter Installation guide | |
---|---|---|
Number of power module free slots | ||
Number of power module filled slots | ||
redundant | No | |
UPS size | WS |
colour | White | |
---|---|---|
depth | 96.9 cm | |
height | 140 cm | |
mounting preference | No preference | |
net weight | 590 kg | |
mounting mode | Not rack-mountable | |
two post mountable | ||
USB compatible | No | |
width | 50 cm |
Network frequency | 45…65 Hz | |
---|---|---|
input voltage limits | 304…477 V | |
inputvolt_other | 380 V 415 V | |
maximum input current | 73 A | |
input harmonic distortion | Less than 3 % for full load | |
input voltage | 400 V 3 phases | |
load power factor | 0.9 leading to 0.9 lagging | |
cos phi | 0.99 |
rated power in W | 40000 W | |
---|---|---|
Maximum configurable power in W | 40000 W | |
harmonic distortion | Less than 3 % | |
output frequency | 50 Hz sync to mains 60 Hz sync to mains | |
outputvolt_other | 380 V 415 V | |
UPS type | Double conversion online | |
output voltage tolerance | +/- 1.5 % | |
output harmonic distortion | < 3% linear load | |
curve equation | Efficiency | |
curve fixed loss | 0.0042 | |
curve load maximum | 100 % | |
curve load minimum | 1 % | |
curve proportional loss | 0.0258 | |
curve square loss | 0.0208 | |
curve X-axis maximum | 100 % | |
curve test cond ID | Curve fit to measured efficiency data. All measurements taken in normal operating mode, at typical environmental conditions, with 400V 50Hz input and 400V 50Hz balanced resistive load (PF = 1.0) Output. | |
curve X-axis minimum | 0 % | |
curve X-axis title | Load | |
curve X-axis units | Percentage | |
curve Y-axis maximum | 100 % | |
curve Y-axis minimum | 50 % | |
curve Y-axis title | Efficiency | |
curve Y-axis units | Percentage | |
graph display | ||
output voltage | 400 V 3 phases | |
Maximum configurable power in VA | 40000 VA | |
rated power in VA | 40000 VA |